Field measurements and modelling of high frequency transients during disconnect switch operations in EHV Substations : Assessment of their effects on Current Transformers

Autores
Pozo, Miguel Dionisio del; Esteban, Daniel A.; Issouribehere, Pedro; Barbera, Gustavo Ariel; Ledesma, Alicia I.; Funes, A.
Año de publicación
2010
Idioma
español castellano
Tipo de recurso
documento de conferencia
Estado
versión publicada
Descripción
The article describes the complete procedure carried out in order to determine the cause of high levels of gases detected in chromatographic determinations performed in Current Transformers (CT) oil. These analyses of gases are normally included in routine maintenance work. The obtained results could evidence some possible damage in the machine insulation. According to the electrical stresses that Current Transformers are typically subjected to, it was presumed that the cause of the possible damaged could be the high-frequency transients that take place during air disconnect switch operations. Therefore, with the aim of determining the presence of such electrical stress, field measurements were performed. A specially designed measuring system was utilized to accomplish this goal. Taking into account the difficulties normally encountered when measuring currents flowing through Current Transformers to ground, especially in terms of accuracy, it was decided to perform voltage measurements. Then, by determining the real frequency response of the CT in the range of interest, it was possible to achieve such currents by computer simulations. In order to achieve accurate results in the simulations, it was necessary to develop an appropriate electrical model of this type of transformers in the analyzed frequency range. Once the model was carefully adjusted, computer simulations were performed. As a result, both shape and magnitude of such currents were also achieved. Finally, one of the Current Transformers with high levels of gases was taken out of service. Then, it was completely disassembled so as to confirm the suspected damage in the insulation. The results yielded in the inspection of the insulation are commented at the end of this work.
Instituto de Investigaciones Tecnológicas para Redes y Equipos Eléctricos (IITREE)
Materia
Ingeniería
electrical stress
current transformer
insulation
measurement
model simulation
Energía Eléctrica
high frequency transiet
HV equipment
Nivel de accesibilidad
acceso abierto
Condiciones de uso
http://creativecommons.org/licenses/by/3.0/
Repositorio
SEDICI (UNLP)
Institución
Universidad Nacional de La Plata
OAI Identificador
oai:sedici.unlp.edu.ar:10915/36418

id SEDICI_2a4a7f3014ce4f1ee5b1f2bb9efb5677
oai_identifier_str oai:sedici.unlp.edu.ar:10915/36418
network_acronym_str SEDICI
repository_id_str 1329
network_name_str SEDICI (UNLP)
spelling Field measurements and modelling of high frequency transients during disconnect switch operations in EHV Substations : Assessment of their effects on Current TransformersPozo, Miguel Dionisio delEsteban, Daniel A.Issouribehere, PedroBarbera, Gustavo ArielLedesma, Alicia I.Funes, A.Ingenieríaelectrical stresscurrent transformerinsulationmeasurementmodel simulationEnergía Eléctricahigh frequency transietHV equipmentThe article describes the complete procedure carried out in order to determine the cause of high levels of gases detected in chromatographic determinations performed in Current Transformers (CT) oil. These analyses of gases are normally included in routine maintenance work. The obtained results could evidence some possible damage in the machine insulation. According to the electrical stresses that Current Transformers are typically subjected to, it was presumed that the cause of the possible damaged could be the high-frequency transients that take place during air disconnect switch operations. Therefore, with the aim of determining the presence of such electrical stress, field measurements were performed. A specially designed measuring system was utilized to accomplish this goal. Taking into account the difficulties normally encountered when measuring currents flowing through Current Transformers to ground, especially in terms of accuracy, it was decided to perform voltage measurements. Then, by determining the real frequency response of the CT in the range of interest, it was possible to achieve such currents by computer simulations. In order to achieve accurate results in the simulations, it was necessary to develop an appropriate electrical model of this type of transformers in the analyzed frequency range. Once the model was carefully adjusted, computer simulations were performed. As a result, both shape and magnitude of such currents were also achieved. Finally, one of the Current Transformers with high levels of gases was taken out of service. Then, it was completely disassembled so as to confirm the suspected damage in the insulation. The results yielded in the inspection of the insulation are commented at the end of this work.Instituto de Investigaciones Tecnológicas para Redes y Equipos Eléctricos (IITREE)2010-07info:eu-repo/semantics/conferenceObjectinfo:eu-repo/semantics/publishedVersionObjeto de conferenciahttp://purl.org/coar/resource_type/c_5794info:ar-repo/semantics/documentoDeConferenciaapplication/pdfhttp://sedici.unlp.edu.ar/handle/10915/36418spainfo:eu-repo/semantics/altIdentifier/url/https://app.box.com/s/743e4c27ba7edc68757cinfo:eu-repo/semantics/openAccesshttp://creativecommons.org/licenses/by/3.0/Creative Commons Attribution 3.0 Unported (CC BY 3.0)reponame:SEDICI (UNLP)instname:Universidad Nacional de La Platainstacron:UNLP2025-09-03T10:32:19Zoai:sedici.unlp.edu.ar:10915/36418Institucionalhttp://sedici.unlp.edu.ar/Universidad públicaNo correspondehttp://sedici.unlp.edu.ar/oai/snrdalira@sedici.unlp.edu.arArgentinaNo correspondeNo correspondeNo correspondeopendoar:13292025-09-03 10:32:20.282SEDICI (UNLP) - Universidad Nacional de La Platafalse
dc.title.none.fl_str_mv Field measurements and modelling of high frequency transients during disconnect switch operations in EHV Substations : Assessment of their effects on Current Transformers
title Field measurements and modelling of high frequency transients during disconnect switch operations in EHV Substations : Assessment of their effects on Current Transformers
spellingShingle Field measurements and modelling of high frequency transients during disconnect switch operations in EHV Substations : Assessment of their effects on Current Transformers
Pozo, Miguel Dionisio del
Ingeniería
electrical stress
current transformer
insulation
measurement
model simulation
Energía Eléctrica
high frequency transiet
HV equipment
title_short Field measurements and modelling of high frequency transients during disconnect switch operations in EHV Substations : Assessment of their effects on Current Transformers
title_full Field measurements and modelling of high frequency transients during disconnect switch operations in EHV Substations : Assessment of their effects on Current Transformers
title_fullStr Field measurements and modelling of high frequency transients during disconnect switch operations in EHV Substations : Assessment of their effects on Current Transformers
title_full_unstemmed Field measurements and modelling of high frequency transients during disconnect switch operations in EHV Substations : Assessment of their effects on Current Transformers
title_sort Field measurements and modelling of high frequency transients during disconnect switch operations in EHV Substations : Assessment of their effects on Current Transformers
dc.creator.none.fl_str_mv Pozo, Miguel Dionisio del
Esteban, Daniel A.
Issouribehere, Pedro
Barbera, Gustavo Ariel
Ledesma, Alicia I.
Funes, A.
author Pozo, Miguel Dionisio del
author_facet Pozo, Miguel Dionisio del
Esteban, Daniel A.
Issouribehere, Pedro
Barbera, Gustavo Ariel
Ledesma, Alicia I.
Funes, A.
author_role author
author2 Esteban, Daniel A.
Issouribehere, Pedro
Barbera, Gustavo Ariel
Ledesma, Alicia I.
Funes, A.
author2_role author
author
author
author
author
dc.subject.none.fl_str_mv Ingeniería
electrical stress
current transformer
insulation
measurement
model simulation
Energía Eléctrica
high frequency transiet
HV equipment
topic Ingeniería
electrical stress
current transformer
insulation
measurement
model simulation
Energía Eléctrica
high frequency transiet
HV equipment
dc.description.none.fl_txt_mv The article describes the complete procedure carried out in order to determine the cause of high levels of gases detected in chromatographic determinations performed in Current Transformers (CT) oil. These analyses of gases are normally included in routine maintenance work. The obtained results could evidence some possible damage in the machine insulation. According to the electrical stresses that Current Transformers are typically subjected to, it was presumed that the cause of the possible damaged could be the high-frequency transients that take place during air disconnect switch operations. Therefore, with the aim of determining the presence of such electrical stress, field measurements were performed. A specially designed measuring system was utilized to accomplish this goal. Taking into account the difficulties normally encountered when measuring currents flowing through Current Transformers to ground, especially in terms of accuracy, it was decided to perform voltage measurements. Then, by determining the real frequency response of the CT in the range of interest, it was possible to achieve such currents by computer simulations. In order to achieve accurate results in the simulations, it was necessary to develop an appropriate electrical model of this type of transformers in the analyzed frequency range. Once the model was carefully adjusted, computer simulations were performed. As a result, both shape and magnitude of such currents were also achieved. Finally, one of the Current Transformers with high levels of gases was taken out of service. Then, it was completely disassembled so as to confirm the suspected damage in the insulation. The results yielded in the inspection of the insulation are commented at the end of this work.
Instituto de Investigaciones Tecnológicas para Redes y Equipos Eléctricos (IITREE)
description The article describes the complete procedure carried out in order to determine the cause of high levels of gases detected in chromatographic determinations performed in Current Transformers (CT) oil. These analyses of gases are normally included in routine maintenance work. The obtained results could evidence some possible damage in the machine insulation. According to the electrical stresses that Current Transformers are typically subjected to, it was presumed that the cause of the possible damaged could be the high-frequency transients that take place during air disconnect switch operations. Therefore, with the aim of determining the presence of such electrical stress, field measurements were performed. A specially designed measuring system was utilized to accomplish this goal. Taking into account the difficulties normally encountered when measuring currents flowing through Current Transformers to ground, especially in terms of accuracy, it was decided to perform voltage measurements. Then, by determining the real frequency response of the CT in the range of interest, it was possible to achieve such currents by computer simulations. In order to achieve accurate results in the simulations, it was necessary to develop an appropriate electrical model of this type of transformers in the analyzed frequency range. Once the model was carefully adjusted, computer simulations were performed. As a result, both shape and magnitude of such currents were also achieved. Finally, one of the Current Transformers with high levels of gases was taken out of service. Then, it was completely disassembled so as to confirm the suspected damage in the insulation. The results yielded in the inspection of the insulation are commented at the end of this work.
publishDate 2010
dc.date.none.fl_str_mv 2010-07
dc.type.none.fl_str_mv info:eu-repo/semantics/conferenceObject
info:eu-repo/semantics/publishedVersion
Objeto de conferencia
http://purl.org/coar/resource_type/c_5794
info:ar-repo/semantics/documentoDeConferencia
format conferenceObject
status_str publishedVersion
dc.identifier.none.fl_str_mv http://sedici.unlp.edu.ar/handle/10915/36418
url http://sedici.unlp.edu.ar/handle/10915/36418
dc.language.none.fl_str_mv spa
language spa
dc.relation.none.fl_str_mv info:eu-repo/semantics/altIdentifier/url/https://app.box.com/s/743e4c27ba7edc68757c
dc.rights.none.fl_str_mv info:eu-repo/semantics/openAccess
http://creativecommons.org/licenses/by/3.0/
Creative Commons Attribution 3.0 Unported (CC BY 3.0)
eu_rights_str_mv openAccess
rights_invalid_str_mv http://creativecommons.org/licenses/by/3.0/
Creative Commons Attribution 3.0 Unported (CC BY 3.0)
dc.format.none.fl_str_mv application/pdf
dc.source.none.fl_str_mv reponame:SEDICI (UNLP)
instname:Universidad Nacional de La Plata
instacron:UNLP
reponame_str SEDICI (UNLP)
collection SEDICI (UNLP)
instname_str Universidad Nacional de La Plata
instacron_str UNLP
institution UNLP
repository.name.fl_str_mv SEDICI (UNLP) - Universidad Nacional de La Plata
repository.mail.fl_str_mv alira@sedici.unlp.edu.ar
_version_ 1842260170733780992
score 13.13397