Field measurements and modelling of high frequency transients during disconnect switch operations in EHV Substations : Assessment of their effects on Current Transformers
- Autores
- Pozo, Miguel Dionisio del; Esteban, Daniel A.; Issouribehere, Pedro; Barbera, Gustavo Ariel; Ledesma, Alicia I.; Funes, A.
- Año de publicación
- 2010
- Idioma
- español castellano
- Tipo de recurso
- documento de conferencia
- Estado
- versión publicada
- Descripción
- The article describes the complete procedure carried out in order to determine the cause of high levels of gases detected in chromatographic determinations performed in Current Transformers (CT) oil. These analyses of gases are normally included in routine maintenance work. The obtained results could evidence some possible damage in the machine insulation. According to the electrical stresses that Current Transformers are typically subjected to, it was presumed that the cause of the possible damaged could be the high-frequency transients that take place during air disconnect switch operations. Therefore, with the aim of determining the presence of such electrical stress, field measurements were performed. A specially designed measuring system was utilized to accomplish this goal. Taking into account the difficulties normally encountered when measuring currents flowing through Current Transformers to ground, especially in terms of accuracy, it was decided to perform voltage measurements. Then, by determining the real frequency response of the CT in the range of interest, it was possible to achieve such currents by computer simulations. In order to achieve accurate results in the simulations, it was necessary to develop an appropriate electrical model of this type of transformers in the analyzed frequency range. Once the model was carefully adjusted, computer simulations were performed. As a result, both shape and magnitude of such currents were also achieved. Finally, one of the Current Transformers with high levels of gases was taken out of service. Then, it was completely disassembled so as to confirm the suspected damage in the insulation. The results yielded in the inspection of the insulation are commented at the end of this work.
Instituto de Investigaciones Tecnológicas para Redes y Equipos Eléctricos (IITREE) - Materia
-
Ingeniería
electrical stress
current transformer
insulation
measurement
model simulation
Energía Eléctrica
high frequency transiet
HV equipment - Nivel de accesibilidad
- acceso abierto
- Condiciones de uso
- http://creativecommons.org/licenses/by/3.0/
- Repositorio
- Institución
- Universidad Nacional de La Plata
- OAI Identificador
- oai:sedici.unlp.edu.ar:10915/36418
Ver los metadatos del registro completo
id |
SEDICI_2a4a7f3014ce4f1ee5b1f2bb9efb5677 |
---|---|
oai_identifier_str |
oai:sedici.unlp.edu.ar:10915/36418 |
network_acronym_str |
SEDICI |
repository_id_str |
1329 |
network_name_str |
SEDICI (UNLP) |
spelling |
Field measurements and modelling of high frequency transients during disconnect switch operations in EHV Substations : Assessment of their effects on Current TransformersPozo, Miguel Dionisio delEsteban, Daniel A.Issouribehere, PedroBarbera, Gustavo ArielLedesma, Alicia I.Funes, A.Ingenieríaelectrical stresscurrent transformerinsulationmeasurementmodel simulationEnergía Eléctricahigh frequency transietHV equipmentThe article describes the complete procedure carried out in order to determine the cause of high levels of gases detected in chromatographic determinations performed in Current Transformers (CT) oil. These analyses of gases are normally included in routine maintenance work. The obtained results could evidence some possible damage in the machine insulation. According to the electrical stresses that Current Transformers are typically subjected to, it was presumed that the cause of the possible damaged could be the high-frequency transients that take place during air disconnect switch operations. Therefore, with the aim of determining the presence of such electrical stress, field measurements were performed. A specially designed measuring system was utilized to accomplish this goal. Taking into account the difficulties normally encountered when measuring currents flowing through Current Transformers to ground, especially in terms of accuracy, it was decided to perform voltage measurements. Then, by determining the real frequency response of the CT in the range of interest, it was possible to achieve such currents by computer simulations. In order to achieve accurate results in the simulations, it was necessary to develop an appropriate electrical model of this type of transformers in the analyzed frequency range. Once the model was carefully adjusted, computer simulations were performed. As a result, both shape and magnitude of such currents were also achieved. Finally, one of the Current Transformers with high levels of gases was taken out of service. Then, it was completely disassembled so as to confirm the suspected damage in the insulation. The results yielded in the inspection of the insulation are commented at the end of this work.Instituto de Investigaciones Tecnológicas para Redes y Equipos Eléctricos (IITREE)2010-07info:eu-repo/semantics/conferenceObjectinfo:eu-repo/semantics/publishedVersionObjeto de conferenciahttp://purl.org/coar/resource_type/c_5794info:ar-repo/semantics/documentoDeConferenciaapplication/pdfhttp://sedici.unlp.edu.ar/handle/10915/36418spainfo:eu-repo/semantics/altIdentifier/url/https://app.box.com/s/743e4c27ba7edc68757cinfo:eu-repo/semantics/openAccesshttp://creativecommons.org/licenses/by/3.0/Creative Commons Attribution 3.0 Unported (CC BY 3.0)reponame:SEDICI (UNLP)instname:Universidad Nacional de La Platainstacron:UNLP2025-09-03T10:32:19Zoai:sedici.unlp.edu.ar:10915/36418Institucionalhttp://sedici.unlp.edu.ar/Universidad públicaNo correspondehttp://sedici.unlp.edu.ar/oai/snrdalira@sedici.unlp.edu.arArgentinaNo correspondeNo correspondeNo correspondeopendoar:13292025-09-03 10:32:20.282SEDICI (UNLP) - Universidad Nacional de La Platafalse |
dc.title.none.fl_str_mv |
Field measurements and modelling of high frequency transients during disconnect switch operations in EHV Substations : Assessment of their effects on Current Transformers |
title |
Field measurements and modelling of high frequency transients during disconnect switch operations in EHV Substations : Assessment of their effects on Current Transformers |
spellingShingle |
Field measurements and modelling of high frequency transients during disconnect switch operations in EHV Substations : Assessment of their effects on Current Transformers Pozo, Miguel Dionisio del Ingeniería electrical stress current transformer insulation measurement model simulation Energía Eléctrica high frequency transiet HV equipment |
title_short |
Field measurements and modelling of high frequency transients during disconnect switch operations in EHV Substations : Assessment of their effects on Current Transformers |
title_full |
Field measurements and modelling of high frequency transients during disconnect switch operations in EHV Substations : Assessment of their effects on Current Transformers |
title_fullStr |
Field measurements and modelling of high frequency transients during disconnect switch operations in EHV Substations : Assessment of their effects on Current Transformers |
title_full_unstemmed |
Field measurements and modelling of high frequency transients during disconnect switch operations in EHV Substations : Assessment of their effects on Current Transformers |
title_sort |
Field measurements and modelling of high frequency transients during disconnect switch operations in EHV Substations : Assessment of their effects on Current Transformers |
dc.creator.none.fl_str_mv |
Pozo, Miguel Dionisio del Esteban, Daniel A. Issouribehere, Pedro Barbera, Gustavo Ariel Ledesma, Alicia I. Funes, A. |
author |
Pozo, Miguel Dionisio del |
author_facet |
Pozo, Miguel Dionisio del Esteban, Daniel A. Issouribehere, Pedro Barbera, Gustavo Ariel Ledesma, Alicia I. Funes, A. |
author_role |
author |
author2 |
Esteban, Daniel A. Issouribehere, Pedro Barbera, Gustavo Ariel Ledesma, Alicia I. Funes, A. |
author2_role |
author author author author author |
dc.subject.none.fl_str_mv |
Ingeniería electrical stress current transformer insulation measurement model simulation Energía Eléctrica high frequency transiet HV equipment |
topic |
Ingeniería electrical stress current transformer insulation measurement model simulation Energía Eléctrica high frequency transiet HV equipment |
dc.description.none.fl_txt_mv |
The article describes the complete procedure carried out in order to determine the cause of high levels of gases detected in chromatographic determinations performed in Current Transformers (CT) oil. These analyses of gases are normally included in routine maintenance work. The obtained results could evidence some possible damage in the machine insulation. According to the electrical stresses that Current Transformers are typically subjected to, it was presumed that the cause of the possible damaged could be the high-frequency transients that take place during air disconnect switch operations. Therefore, with the aim of determining the presence of such electrical stress, field measurements were performed. A specially designed measuring system was utilized to accomplish this goal. Taking into account the difficulties normally encountered when measuring currents flowing through Current Transformers to ground, especially in terms of accuracy, it was decided to perform voltage measurements. Then, by determining the real frequency response of the CT in the range of interest, it was possible to achieve such currents by computer simulations. In order to achieve accurate results in the simulations, it was necessary to develop an appropriate electrical model of this type of transformers in the analyzed frequency range. Once the model was carefully adjusted, computer simulations were performed. As a result, both shape and magnitude of such currents were also achieved. Finally, one of the Current Transformers with high levels of gases was taken out of service. Then, it was completely disassembled so as to confirm the suspected damage in the insulation. The results yielded in the inspection of the insulation are commented at the end of this work. Instituto de Investigaciones Tecnológicas para Redes y Equipos Eléctricos (IITREE) |
description |
The article describes the complete procedure carried out in order to determine the cause of high levels of gases detected in chromatographic determinations performed in Current Transformers (CT) oil. These analyses of gases are normally included in routine maintenance work. The obtained results could evidence some possible damage in the machine insulation. According to the electrical stresses that Current Transformers are typically subjected to, it was presumed that the cause of the possible damaged could be the high-frequency transients that take place during air disconnect switch operations. Therefore, with the aim of determining the presence of such electrical stress, field measurements were performed. A specially designed measuring system was utilized to accomplish this goal. Taking into account the difficulties normally encountered when measuring currents flowing through Current Transformers to ground, especially in terms of accuracy, it was decided to perform voltage measurements. Then, by determining the real frequency response of the CT in the range of interest, it was possible to achieve such currents by computer simulations. In order to achieve accurate results in the simulations, it was necessary to develop an appropriate electrical model of this type of transformers in the analyzed frequency range. Once the model was carefully adjusted, computer simulations were performed. As a result, both shape and magnitude of such currents were also achieved. Finally, one of the Current Transformers with high levels of gases was taken out of service. Then, it was completely disassembled so as to confirm the suspected damage in the insulation. The results yielded in the inspection of the insulation are commented at the end of this work. |
publishDate |
2010 |
dc.date.none.fl_str_mv |
2010-07 |
dc.type.none.fl_str_mv |
info:eu-repo/semantics/conferenceObject info:eu-repo/semantics/publishedVersion Objeto de conferencia http://purl.org/coar/resource_type/c_5794 info:ar-repo/semantics/documentoDeConferencia |
format |
conferenceObject |
status_str |
publishedVersion |
dc.identifier.none.fl_str_mv |
http://sedici.unlp.edu.ar/handle/10915/36418 |
url |
http://sedici.unlp.edu.ar/handle/10915/36418 |
dc.language.none.fl_str_mv |
spa |
language |
spa |
dc.relation.none.fl_str_mv |
info:eu-repo/semantics/altIdentifier/url/https://app.box.com/s/743e4c27ba7edc68757c |
dc.rights.none.fl_str_mv |
info:eu-repo/semantics/openAccess http://creativecommons.org/licenses/by/3.0/ Creative Commons Attribution 3.0 Unported (CC BY 3.0) |
eu_rights_str_mv |
openAccess |
rights_invalid_str_mv |
http://creativecommons.org/licenses/by/3.0/ Creative Commons Attribution 3.0 Unported (CC BY 3.0) |
dc.format.none.fl_str_mv |
application/pdf |
dc.source.none.fl_str_mv |
reponame:SEDICI (UNLP) instname:Universidad Nacional de La Plata instacron:UNLP |
reponame_str |
SEDICI (UNLP) |
collection |
SEDICI (UNLP) |
instname_str |
Universidad Nacional de La Plata |
instacron_str |
UNLP |
institution |
UNLP |
repository.name.fl_str_mv |
SEDICI (UNLP) - Universidad Nacional de La Plata |
repository.mail.fl_str_mv |
alira@sedici.unlp.edu.ar |
_version_ |
1842260170733780992 |
score |
13.13397 |